Bible Entry: Dew Point and Bathroom Ceiling Condensation — Explained Simply, and Why It Shifts in a Prairie Winter

Category: E — Moisture, Mould & Bathroom Damage Entry type: Building physics fundamentals (computed, with every input stated) Version: 1.0 (draft — pending technical review) Master list reference: #33


Answer-First Summary

Water appears on a bathroom surface when that surface is colder than the dew point of the air touching it. That is the whole mechanism. Everything else — mirrors fogging, droplets on the ceiling, grey mould lines along the joists, mould in the corner above the tub — is that one rule playing out on different surfaces.

Two numbers decide it: how much water is in the air (which sets the dew point), and how cold the coldest surface is (which is set by insulation and outdoor temperature).

The calculations in this entry show three things:

  1. A properly insulated ceiling almost never condenses. It stays within about one degree of room temperature even at −30°C outside. Condensation there needs the room to be near 100% humidity.
  2. A gap in the insulation changes everything. Where insulation is missing — around a fan housing, at a thin eave — the ceiling surface can be ten to twenty degrees colder. At −20°C outside, such a spot reaches dew point when the room is at 37% relative humidity, which is ordinary dry winter air, before anyone has showered.
  3. In very cold weather, the exhaust fan works better, not worse. Outdoor air at −20°C holds almost no water, so every cubic metre the fan exchanges takes out about half again as much moisture as the same exchange on the coast in winter.

So in a cold climate, a ceiling that shows a stripe or a ring of mould is usually reporting an insulation defect, and the fan is only part of the fix.


1. Dew Point, Simply

Warm air can hold more water vapour than cold air. Relative humidity is how full the air is, as a percentage of what it could hold at its current temperature. Because the capacity changes with temperature, relative humidity changes whenever the temperature does, even if not a drop of water is added or removed.

Dew point is the temperature at which a given parcel of air would be completely full — 100% relative humidity. Cool it any further and water comes out as liquid. Unlike relative humidity, dew point does not change when the air warms or cools; it only changes when water is added or removed. It is the more honest measure of how wet the air is.

The practical rule follows directly:

Any surface colder than the air's dew point gets wet.

Dew points of typical bathroom air

Computed with the Magnus approximation (coefficients 17.625 and 243.04 °C; see Sources):

Room temperature40% RH50%60%70%80%90%
20 °C6.0 °C9.312.014.416.418.3
22 °C7.8 °C11.113.916.318.420.3
24 °C9.6 °C12.915.818.220.322.3

Read the bottom-right corner. During and just after a hot shower, a bathroom at 24°C and 90% RH has a dew point above 22°C. The mirror, the window glass, a cold exterior wall — anything below about 22°C — will run with water. That is why the mirror fogs first: it is usually the coldest smooth surface in the room, and the water is visible on it.


2. How Cold Is the Ceiling? It Depends Almost Entirely on Insulation

A top-floor bathroom ceiling has the heated room on one side and an attic on the other. In a vented attic in winter, the attic is close to outdoor temperature. The ceiling surface settles somewhere between the two, and where it settles depends on how much thermal resistance sits above it.

The interior surface temperature of a layered assembly, in steady state, is:

T_surface = T_room − (T_room − T_attic) × (R_inside_film ÷ R_total)

Inputs used here (all stated so they can be checked):

  • Room 22 °C.
  • Inside surface film RSI 0.11 (still air, heat flowing upward).
  • Drywall RSI 0.08.
  • Attic-side film RSI 0.11.
  • Attic temperature taken as equal to outdoor temperature.

Three ceiling conditions:

Ceiling conditionInsulation+5 °C outside−10 °C−20 °C−30 °C
Well insulated (about R-40)RSI 7.021.7 °C21.521.421.2
Thin, e.g. compressed at the eaveRSI 1.020.6 °C19.318.417.6
Void — no insulationnone15.8 °C10.36.62.9

The well-insulated ceiling barely moves, from coastal winter to deep Prairie cold. The uninsulated spot tracks the weather — at −30 °C outside it is only about 3 °C on the room side.

What that means for condensation

Combining the two tables gives the room humidity at which each ceiling condition starts to get wet, with the room at 22 °C:

Ceiling condition+5 °C outside−10 °C−20 °C−30 °C
Well insulated98% RH97%96%95%
Thin at the eave92% RH85%80%76%
Void68% RH47%37%29%

The bottom row is the point of this entry. In a Calgary, Regina or Winnipeg cold snap, an uninsulated patch of bathroom ceiling reaches dew point when the room is at 29–37% relative humidity. Indoor air in a Prairie winter often sits in that range anyway. That spot can condense without anyone showering. After a shower, it is soaked.

On the coast, at +5 °C outside, the same void does not condense until the room passes 68%. A shower still gets it there — but it takes a shower.


3. You Don't Need Droplets to Get Mould

Visible condensation is not the threshold for mould. Research for the International Energy Agency's Annex 14, Condensation and Energy, adopted as a design criterion that mould germination becomes probable where the monthly mean relative humidity at the surface exceeds 80%.

A surface colder than the room has a higher relative humidity than the room, even when it is dry to the touch. Applying the 80% surface criterion with the room at 22 °C:

Ceiling conditionRoom RH at which the cold spot reaches 80% surface RH
+5 °C outside−10 °C−20 °C−30 °C
Well insulated79%78%77%76%
Thin at the eave73%68%64%61%
Void54%38%30%23%

The Annex 14 criterion is a monthly average, and these are steady-state snapshots, so the comparison is indicative, not a prediction. But the direction is unambiguous. Over a cold month, a bathroom ceiling with an insulation void spends long periods in mould-growth territory without ever showing a droplet. That is how mould appears on a ceiling that the homeowner swears is never wet.


4. Reading the Patterns on a Ceiling

The physics explains the shapes that show up in practice. The mapping below is our field reading, not something the calculations prove; see the source tiers.

  • A ring or patch around the fan grille. Insulation is often pulled back or missing around the fan housing, and a metal housing conducts heat well. The ceiling right around the fan is frequently the coldest spot in the room — which is why mould around a fan grille does not on its own prove the fan is failing.
  • A band along the exterior wall or in the corner. The eave is where attic insulation is thinnest, because the roof slopes down to meet the top of the wall. This is the "thin at the eave" row.
  • Parallel stripes at regular spacing. Lines at joist or truss spacing, light or dark, show where heat moves differently through framing than through the insulated bays between. The framing is a thermal bridge; the stripes are dust or mould tracking the temperature difference. (A two-dimensional effect that the one-dimensional calculation above does not model.)
  • Evenly spread speckling across the whole ceiling. Points more to persistently high room humidity than to a single cold spot.

The first three are insulation and air-sealing problems that a better fan reduces but does not fix. The fourth is the case a properly working fan addresses most directly.


5. The Fan's Job, in Dew-Point Terms

The fan's job is to bring the room's dew point back down below the temperature of the coldest surface, and to do it quickly.

Cold air is dry air — so ventilation works harder in a Prairie winter

How much water the fan removes depends on the difference between the moisture in the bathroom air and the moisture in the air that replaces it. Outdoor air in deep cold holds very little:

AirMoisture content
Outdoor, saturated, +5 °C5.4 g of water per kg of air
Outdoor, saturated, −10 °C1.8 g/kg
Outdoor, saturated, −20 °C0.8 g/kg
Outdoor, saturated, −30 °C0.3 g/kg
Bathroom after a shower, 22 °C at 90% RH14.9 g/kg
Ordinary indoor, 22 °C at 40% RH6.6 g/kg

Even fully saturated, −20 °C outdoor air carries less than a tenth of the water in post-shower bathroom air. Replacing a kilogram of post-shower air with it removes about 14 g of water. On the coast in winter, where outdoor air at +5 °C is often near saturation, the same exchange removes about 9.5 g. Per unit of air exchanged, a fan in a Prairie winter removes roughly 1.5 times as much moisture as the same fan on the coast.

(Replacement air reaches the bathroom by way of the rest of the house, warmed on the way, but its water content is still set by where it came from. The figures above are saturated, which flatters the coast: real outdoor air is usually drier than saturated, and at sub-zero temperatures the saturation figures are slightly lower again over ice.)

This is why the coastal problem and the Prairie problem are different. On the coast the cold spots are milder but the replacement air is wet, so moisture lingers. On the Prairies the replacement air is extremely dry but the cold spots are severe. The coastal case is the subject of master-list entry #103; the Prairie case is #104.

How long it takes

For a well-mixed room, the excess moisture decays roughly exponentially at the air-change rate. A 6 × 9 ft bathroom with 8 ft ceilings, ventilated at 53 CFM (the NBC 2020 model-code bathroom exhaust figure of 25 L/s), gets about 7.4 air changes per hour. After 20 minutes, about 8% of the shower's excess moisture would remain in the air. At 5 air changes per hour, about 19% would remain.

That is an idealised figure. Towels, grout, drywall and paint absorb moisture during a shower and release it slowly afterwards, so real drying takes longer than the air-change arithmetic suggests. It is the physical basis of the advice to run the fan well beyond the end of the shower, covered in the 20-minute entry (D01).


Common Misconceptions

  • "If the humidity is low, there can't be condensation." Relative humidity is measured at room temperature. A cold enough surface condenses even when the room reads 30–40%.
  • "Mould around the fan means the fan has failed." It often means the ceiling around the fan housing is cold because insulation is missing there.
  • "Bigger fan, problem solved." A bigger or better-ducted fan lowers the room's dew point faster. It does not warm a cold spot. Where a ceiling void reaches dew point at 37% RH, no fan keeps the room permanently below that during and after a shower.
  • "Venting is useless when it's −30 outside." The opposite: very cold outdoor air is very dry, so each air change removes more moisture than in mild weather.
  • "No droplets, no mould risk." The established mould criterion is 80% relative humidity at the surface, averaged over a month — reachable without visible condensation.
  • "The coast has the worst condensation problems." The coast has the most persistent humidity. The Prairies have the coldest surfaces. They are different problems.

When to Consult a Professional

  • Mould or staining concentrated around the fan grille, along an exterior wall, or in a pattern at joist spacing — these point to insulation or air-sealing defects that need attic access to assess.
  • Any top-floor bathroom with a ceiling that condenses in cold weather even when the fan is used properly.
  • Any attic where insulation has been disturbed for a fan installation and may not have been replaced.
  • Visible mould over more than a small area, which raises questions this entry does not address — see the moisture-mould-paint entry (E01) and the mould-versus-stain entry (E02).

Nothing in this entry is a diagnosis of a specific ceiling. Surface temperatures, insulation condition and air leakage can only be confirmed on site, ideally with a thermal camera in cold weather.


Sources, by tier

Tier 1 — Established physics and published criteria

  • Dew point formula: Magnus-form approximation with coefficients a = 17.625 and b = 243.04 °C, as given in B. McNoldy, Calculate Temperature, Dewpoint, or Relative Humidity (University of Miami), which cites O. A. Alduchov and R. E. Eskridge, "Improved Magnus' form approximation of saturation vapor pressure," Journal of Applied Meteorology 35 (1996): 601–609. Over liquid water; values below 0 °C are slightly high relative to saturation over ice.
  • Mould criterion: H. Hens and E. Senave, "IEA-Annex 14: Condensation and Energy — Aims, Methodology, Results", KU Leuven: mould germination probable where monthly mean surface RH exceeds 80%. Annex 14 reports dated 1990.
  • National code figure: NBC 2020 9.32.3.7.(4), bathroom supplemental exhaust ≥ 25 L/s.

Tier 2 — Calculation inputs and method (stated so any figure can be recomputed)

  • Steady-state, one-dimensional series-resistance model. Inside film RSI 0.11 (still air, heat flow upward), drywall RSI 0.08, attic-side film RSI 0.11, attic temperature taken equal to outdoor. Insulation levels of RSI 7.0 and RSI 1.0 are illustrative, not code figures. Film and drywall values are standard textbook values, not drawn from a document read for this entry.
  • Moisture contents computed from the same saturation formula at sea-level pressure (1013.25 hPa).
  • Air-change decay assumes a well-mixed room, no ongoing moisture source, and no release from surfaces.
  • Outdoor temperatures of +5, −10, −20 and −30 °C are illustrative of the range from coastal BC to the Prairies. They are not the code design temperatures for specific locations.

Not modelled: stratification (air at the ceiling is warmer and wetter than mid-room); two-dimensional heat flow at framing and fan housings; air leakage, which can move far more moisture than diffusion; radiation to a cold night sky through the roof; and the moisture that surfaces absorb and re-release.

Tier 3 — Bathroom Fan Pros field experience

  • The mapping of ceiling patterns to causes in §4 is our field reading. The patterns are consistent with the physics, but we have not published thermal images or case documentation to support them. Annotated thermal images of these patterns, taken in cold weather, would be the single strongest addition to this entry.