Bible Entry: CSA, HVI and ENERGY STAR — What Each Mark on a Bathroom Fan Actually Verifies

Category: F — Code, Standards & Compliance Entry type: Standards explainer (read from primary sources) Version: 1.0 (draft — pending technical review) Master list reference: #40


Answer-First Summary

A bathroom fan box can carry three kinds of mark. They answer three different questions, and only one of them is a legal requirement.

MarkQuestion it answersRequired?
Electrical certification mark — CSA, cUL, cETL and othersIs this product safe to connect to a Canadian electrical installation?Yes. Legally required.
HVI-CertifiedAre the airflow, sound and power figures true, measured at a defined pressure?No — voluntary
ENERGY STARDoes it meet a minimum efficiency and a maximum noise level?No — voluntary

The most common confusion is treating the CSA mark as a quality or performance mark. It is neither. It means the fan has been certified as electrically safe to a Canadian product standard. It says nothing about how much air the fan moves or how loud it is.

The second confusion is that "CSA" is required specifically. It is not. Canadian rules require certification by a body accredited by the Standards Council of Canada. CSA Group is one of about two dozen such bodies.


1. The Electrical Certification Mark — the One That's Required

1.1 The rule

The Canadian Electrical Code, Part I, Rule 2-024 requires that electrical equipment used in electrical installations be approved. The Code defines "approved" as equipment "certified by a Certification Body accredited by the Standards Council of Canada" (as quoted in UL's Acceptance of Electrical Equipment in Canada).

Provinces enforce this through their own regulations. In British Columbia, section 21(1) of the Electrical Safety Regulation requires that regulated electrical equipment bear evidence of a mark or label of a certification agency, or an approval label issued under section 10 of the Safety Standards Act. Technical Safety BC's bulletin Approved Certification Marks for Electrical Products (B-E3 071019 3, Revision 13, 22 May 2024) sets out what is acceptable as evidence of approval in BC. Ontario's Electrical Safety Authority publishes an equivalent list of recognized marks; other provinces have parallel arrangements.

A bathroom exhaust fan is permanently connected electrical equipment. It falls squarely under this requirement.

1.2 It doesn't have to say "CSA"

The Standards Council of Canada publishes the marks it recognizes for electrical products. Its list includes, among others, the Canadian Standards Association (CSA Group), UL, Intertek, QPS, TÜV Rheinland, TÜV SÜD, Nemko, SGS, NSF and the Electrical Safety Authority — roughly two dozen organizations.

Any of those marks, applied for the Canadian market, is acceptable evidence of approval. A fan bearing a cETL or cUL mark and no CSA mark is as legal to install as one bearing a CSA mark.

1.3 Watch for US-only marks

Several of these organizations certify to both American and Canadian standards and indicate which with a small "C" and/or "US" beside the mark. A mark showing certification to US standards only is not evidence of Canadian approval. Fans bought from US online sellers are where this shows up.

This paragraph is trade practice rather than something the bulletins cited above spell out; see the source tiers. Check the marking against the certifier's own description, or against the provincial list of recognized marks, when in doubt.

1.4 What the fan is certified to

For most bathroom fans, the relevant Canadian product safety standard is CSA C22.2 No. 113, Fans and ventilators — currently the eleventh edition, published 2018 and reaffirmed 2023. It is a Part II standard of the Canadian Electrical Code: a product safety standard. Its scope includes wall-insert and ceiling-insert fans, power ventilators, and bathtub and shower-stall fans. Duct fans and some other categories are covered by a different standard, CSA C22.2 No. 60335-2-80.

C22.2 No. 113 is concerned with electrical safety — shock, fire, construction, marking. It does not rate airflow or loudness.

1.5 Where the safety certification matters most in a bathroom

Whether a fan may be installed over a bathtub or inside a shower enclosure is a question for its certification and the manufacturer's instructions, not for its airflow rating. The product standard covers bathtub and shower-stall fans as a category, and a fan intended for that location is certified and marked for it. A fan not certified for that location should not be put there, however well it performs. Where a fan is permitted in that location, its instructions commonly set conditions such as GFCI protection. Read the marking and the instructions on the specific product.


2. HVI Certification — the Performance Mark

The HVI-Certified label means a fan's airflow, sound and power ratings were tested to HVI's procedures and are subject to annual random verification. It is voluntary.

The detail — rating pressures, tolerances, the inline-fan gap — is in its own entry, HVI Test Standards. The short version for this comparison:

  • A ceiling bathroom fan's certified airflow is at 0.1 in. w.g. (≈25 Pa), which is the pressure the National Building Code uses to rate a bathroom supplemental fan.
  • Verification passes a product at 90% of its certified airflow.
  • The NBC names HVI 915 as one of the two sound-rating methods it accepts for its sone limits (Table 9.32.3.10.-B). The other is CAN/CSA-C260-M.

Two "CSA" standards that are often run together

CSA appears on the fan's safety label (C22.2 No. 113, a safety standard). CSA also published CAN/CSA-C260-M90, Rating the Performance of Residential Mechanical Ventilating Equipment, which the National Building Code names as an alternative sound-rating method. Different documents, different purposes. A "CSA" mark on the box is the safety certification. It is not evidence of a C260 performance rating.

The sone limits the NBC sets depend on which method the rating came from: for a bathroom supplemental fan, 2.5 sones under C260-M or 3.5 sones under HVI 915 (NBC 2020 Table 9.32.3.10.-B).

C260 has been withdrawn. The Standards Council of Canada's standards database lists CAN/CSA-C260-M90 (R2007) as withdrawn ("Annulée"). NBC 2020 still names it. The likely practical consequence — an inference, not something either source states — is that current products are rated to HVI 915, and the HVI 915 column of the NBC sone table (3.5 sones for a bathroom fan) is the one that applies to most fans now on the market. A sone figure on a current spec sheet should be read as an HVI 915 figure unless it says otherwise.


3. ENERGY STAR — the Efficiency Mark

3.1 Which specification applies in Canada

Natural Resources Canada administers ENERGY STAR in Canada. For most products, including ventilating fans, ENERGY STAR Canada links directly to the United States specification rather than publishing its own (exceptions it names include HRVs/ERVs and windows, doors and skylights).

The current specification is ENERGY STAR Ventilating Fans Version 4.2 (Rev. April 2024). The requirements in this generation of the specification took effect on 1 October 2015.

3.2 The criteria for bathroom fans

ENERGY STAR v4.2, Table 2 (bathroom and utility room fans):

AirflowMinimum efficacyMaximum sound
10 – 89 CFM2.8 CFM/W2.0 sones
90 – 200 CFM3.5 CFM/W2.0 sones
201 – 500 CFM (max speed)4.0 CFM/W3.0 sones

In-line fans have efficacy requirements (3.8 CFM/W; lower with MERV filtration) but no sone limit, consistent with HVI having no sound certification for inline fans.

Further requirements:

  • Rating pressure: bathroom fans are assessed at 0.1 in. w.g.; inline fans at 0.20 in. w.g. (§4.C, Table 5).
  • Installed-performance test: a bathroom fan must deliver at 0.25 in. w.g. at least 70% of the airflow it delivers at 0.1 in. w.g. (§3.C). For multi-speed fans this applies at high speed.
  • Multi-speed fans: fans with three or fewer speeds must meet the criteria at every speed; fans with more speeds or a continuous dial must meet them at maximum, minimum and a midpoint (§3.A.ii).
  • Test methods: HVI 916 or ANSI/AMCA 210 for airflow; HVI 915 or ANSI/AMCA 300 with AMCA 311 for sound (§4.B).
  • Certification: by an EPA-recognized certification body, tested in an EPA-recognized laboratory.
  • Warranty: at least one year.
  • Lights, sensors and timers are allowed and are excluded from the efficacy calculation.
  • Fans with heat lamps or resistance heaters are not eligible (§2.B).

3.3 The two ENERGY STAR criteria that matter most for performance

The 70% rule is the most useful thing ENERGY STAR measures. It is a test of how steep the fan curve is. A fan that holds 70% or more of its airflow when the resistance rises from 0.1 to 0.25 in. w.g. copes better with real duct runs than one whose airflow collapses as resistance rises. ENERGY STAR is the only one of the three marks that sets a pass/fail bar on that property. For anyone worried about delivered airflow rather than rated airflow, this is the most relevant line in the specification.

0.25 in. w.g. is also about 62 Pa — the pressure the NBC uses to rate a principal ventilation fan in an exhaust-only system (Table 9.32.3.10.-A).

The multi-speed rule protects the low speed. HVI certifies only maximum speed unless the manufacturer chooses otherwise. ENERGY STAR requires the criteria to be met at every speed (up to three). For a two-speed fan running continuously on low as a principal ventilator, the ENERGY STAR mark is evidence that the low-speed setting has been tested — something the HVI label alone does not guarantee.

3.4 ENERGY STAR is quieter than the code requires

For a bathroom fan up to 200 CFM, ENERGY STAR allows a maximum of 2.0 sones. The NBC permits a bathroom supplemental fan 2.5 sones (C260-M) or 3.5 sones (HVI 915). An ENERGY STAR bathroom fan in that range meets the NBC sone limits by a comfortable margin, whichever test method was used.

3.5 What efficacy is worth

Efficacy is airflow per watt. The minimums set an upper bound on power draw:

FanMinimum efficacyMaximum power draw
50 CFM2.8 CFM/W≈17.9 W
80 CFM2.8 CFM/W≈28.6 W
110 CFM3.5 CFM/W≈31.4 W

For a fan switched on for twenty minutes after a shower, power draw barely matters. For a fan running continuously as a principal ventilation fan, it does:

Continuous drawEnergy per year
6 W≈53 kWh
12 W≈105 kWh
20 W≈175 kWh
35 W≈307 kWh

Efficacy matters most where the fan runs all the time — which is the case for principal ventilation, and the case ENERGY STAR's per-speed rule addresses.


4. Putting the Three Together

QuestionLook for
Can it legally be installed?An SCC-recognized certification mark for Canada (CSA, cUL, cETL, etc.)
Can it go over the tub or in the shower?Certification and marking for that location, and the manufacturer's instructions
Does it meet the NBC 25 L/s bathroom figure?HVI-certified airflow at 0.1 in. w.g., with margin above ≈53 CFM
Is it within the NBC sone limit?HVI 915 or C260-M sone rating, against Table 9.32.3.10.-B
Will it hold airflow on a real duct run?ENERGY STAR's 70%-at-0.25 test, or the HVI curve
Is the low speed tested?ENERGY STAR (all speeds), or HVI certification at that speed
Is it cheap to run continuously?Efficacy (CFM/W) — ENERGY STAR minimums

Only the first row is a legal requirement for the product itself. The code-compliance rows (25 L/s, sone limit) apply to the installation, and HVI or C260 ratings are how they are demonstrated.


Common Misconceptions

  • "The CSA mark means it's a good fan." It means it is certified as electrically safe. It says nothing about airflow or noise.
  • "It has to be CSA." Any certification body accredited by the Standards Council of Canada will do. cUL and cETL are as valid as CSA.
  • "A UL mark is a UL mark." A mark certifying to US standards only is not evidence of Canadian approval.
  • "ENERGY STAR means it moves more air." ENERGY STAR sets efficiency and noise limits, plus a curve-steepness test. It does not set a minimum airflow.
  • "My heater-fan combo is ENERGY STAR." Fans with heat lamps or resistance heaters are not eligible under the current specification.
  • "Any fan can go over a shower if it's on a GFCI." The location has to be permitted by the product's certification and instructions first.
  • "CSA rates fan performance." CSA C260-M was a performance rating standard, and the NBC still names it for sone ratings, but it has been withdrawn — and the CSA mark on a fan's label is its safety certification, not a C260 rating.

When to Consult a Professional

  • Any fan bought from outside Canada, or any fan whose label does not clearly show certification for the Canadian market.
  • Any installation over a bathtub or within a shower enclosure.
  • Any fan intended to run continuously as the dwelling's principal ventilation fan, where low-speed performance and power draw both matter.
  • Any combination fan with a heater, which carries its own electrical load and installation requirements.

In every province in scope, electrical work on a permanently connected fan is regulated. Who may do it, and when a permit is required, varies by province and is covered in the provincial entries.


Sources, by tier

Tier 1 — Primary documents

Tier 2 — Secondary or practice sources

  • CE Code Rule 2-024 and its definition of "approved," as quoted in UL's Acceptance of Electrical Equipment in Canada. The CE Code itself was not consulted for this entry.
  • The "C"/"US" indicator practice (§1.3): trade practice; not stated in the regulator bulletins read.
  • The statement that fans permitted over a tub or shower commonly require GFCI protection by their instructions (§1.5): trade practice; product-specific.

Not verified: whether bathroom exhaust fans are covered by Canada's federal Energy Efficiency Regulations. The NRCan ventilating-fans page was unavailable during research. We have no evidence that they are, and this entry does not claim they are not.